The Core Decides What the Wall Can Do
Two panels can look identical from the clean side and behave nothing alike. The skin sets the finish; the core sets the fire class, the rigidity, what the panel releases into the room, and how much it insulates.
This guide compares the four cores in the current range, and the two ways they are built — handmade with an internal steel frame and machine-made on a continuous line. It assumes the panel-selection framework is already settled (see the cleanroom wall panel selection guide); what follows is the core decision underneath it.
Four Cores, Four Jobs
|
Criterion |
||||
|
Fire class |
Class A, non-combustible metal skin and core |
Class A, non-combustible inorganic core |
Grade B1, near-zero smoke, zero halogen |
Grade B1 / B2, flame retardant |
|
Core density |
50 - 65 kg/m³ |
120 - 150 kg/m³ (handmade); 100 - 120 kg/m³ (machine-made) |
Rigid closed-cell foam |
12 - 18 kg/m³ |
|
Thermal conductivity |
≤ 0.065 W/(m·k) |
Insulating mineral core |
≤ 0.022 W/(m·k) |
≤ 0.038 W/(m·k) |
|
Sound insulation |
Dampens vibration |
≥ 32 dB at 50 mm (handmade); ≥ 30 dB (machine-made) |
— |
— |
|
Outgassing |
None — 100% metallic, non-particulating |
Inorganic; contained by perimeter steel sealing |
Closed-cell, no nutrient substrate |
Closed-cell foam |
|
Walk-on ceiling |
Yes — honeycomb rigidity over large spans |
Yes with the reinforced frame |
Yes with the steel skeleton |
No — non-walkable ceiling |
|
Cost position |
Premium |
Mid to premium |
Premium |
Economy |
Decision 1: Fire Performance
Three different claims sit in this table, and they are not interchangeable.
• Class A, non-combustible. Rock wool and aluminum honeycomb are inorganic. The honeycomb panel is metal in both skin and core, so it reaches Class A without chemical flame retardants and produces no smoke or toxic fumes under heat exposure. Rock wool is equally non-combustible as a mineral core.
• Grade B1 with near-zero smoke. Phenolic foam is a thermoset. Under fire it carbonizes into a stable protective char layer rather than melting, dripping or collapsing, with a smoke density rating below 5 and zero halogen gas release. That last point matters beyond evacuation: halogen gases are corrosive and attack electronics, sensors and switchgear.
• B1 / B2 flame retardant. EPS relies on flame-retardant additives. It is a legitimate barrier for general cleanrooms, packaging areas and temperature-controlled warehouses — not the same claim as a non-combustible core.
If the wall is a fire compartment boundary, the decision is effectively made above B2.
Decision 2: What Must the Wall Carry?
Rigidity is where cores separate most visibly.
• Aluminum honeycomb uses expanded hexagonal foil to deliver multi-directional rigidity and flatness over large spans, which is why it is used for walk-on ceilings carrying filtration and lighting loads. Despite a metal core it is ultra-light, reducing the load on the support grid.
• Rock wool at 120-150 kg/m³ combined with the manual frame gives high compressive strength and supports walk-on ceilings and large modular walls subject to mechanical stress.
• Phenolic relies on the internal cold-drawn galvanized steel skeleton to distribute load across the panel for walk-on access to FFUs, ductwork and sprinklers.
• EPS is the lightest core. Its compressive strength suits general walls and non-walkable ceilings only.
The practical rule: if maintenance staff will walk the ceiling, the core must be paired with a frame designed for it — and EPS is out.
Decision 3: What the Panel Releases
For ISO Class 1-5 environments, outgassing and particle shedding decide the core.
• Aluminum honeycomb is completely inorganic — it does not release gases, odors or particles over time, which is why it is specified for the tightest classifications.
• Rock wool is inorganic but fibrous, so containment is the issue. Handmade panels seal the perimeter with galvanized steel to give zero fiber leakage — a detail to confirm, not assume, on any rock wool panel.
• Phenolic is a closed-cell, non-organic core: no nutrient substrate for microbial growth.
• EPS is closed-cell and cleanable, which is adequate for its intended general-purpose zones.
Decision 4: Thermal and Acoustic
The numbers in the listings point in different directions, and the right choice depends on which one is the constraint:
• Thermal: phenolic leads at ≤ 0.022 W/(m·k), EPS follows at ≤ 0.038, aluminum honeycomb sits at ≤ 0.065.
• Acoustic: rock wool is the acoustic core — ≥ 32 dB at 50 mm for the handmade panel and ≥ 30 dB for the machine-made, which is why it is used around mechanical production areas.
If the room is next to a compressor or a packaging line, thermal performance alone will not solve the noise; if the room is a cold store, the acoustic argument is secondary.
Decision 5: Handmade or Machine-Made?
The phenolic listing publishes the clearest version of a pattern that applies across the families:
|
Criterion |
||
|
Internal frame |
Cold-drawn galvanized steel skeleton |
No frame — continuous bonding only |
|
Structural rigidity |
Walk-on ceiling rated, high load-bearing |
Standard wall, non-walkable ceiling |
|
Factory cutouts |
Pre-reinforced for doors, windows, FFUs |
On-site cutting required |
|
Edge sealing |
Manual perimeter steel band, superior airtightness |
Standard tongue-and-groove joint |
|
Customization |
Any dimension or configuration |
Standard modular widths |
|
Cost |
Premium |
Cost-effective for large areas |
|
Best for |
Mission-critical GMP suites, vaccine labs, semiconductor fabs |
General fire-rated cleanrooms, cold storage |
Machine-made is not "worse" — it is more consistent and far cheaper per square metre, with automated precision that gives uniform thickness and flatness and faster installation. Handmade buys reinforced edges, factory-prepared openings, tighter perimeter sealing and arbitrary dimensions.
Two practical consequences:
•